Closed-loop systems eliminate water loss by evaporation and algae & bacteria problems.
AquaSaver
Packaged Systems (ASP series)
Energy Saving Control Panel
Standard in ASP series and optional in AS series heat exchangers. Includes power-on/off switch, power-on indicator, fan motor starter(s), and fan cycling thermostat. Fan cycling saves energy and provides temperature control under varying load and ambient conditions.
For longevity and dependability, we recommend Kleen-Water Filters which are 99.0% efficient down to 1 micron. For point of installation see Typical Aqua Saver installation.
| MODEL | PORT SIZE | MAX.PRESS. | MAX | MAX TEMP | DIMENSIONS | APPROX. SHIPPING WT. |
TYPE | |||
| INCHES | ||||||||||
| NPT-IN | PSIG | GPM | Deg. F | A | B | C | D | (LBS) | ||
| KW25 | 1 | 300 | 25 | 225 | 161/4 | 41/2 | - | 15/16 | 15 | T |
| KW50 | 1 1/2 | 300 | 50 | 225 | 205/8 | 57/16 | - | 1 1/4 | 20 | T |
| KW100 | 2 1/2 | 300 | 100 | 225 | 273/4 | 67/8 | - | 1 3/4 | 35 | T |
| KW150 | 2 1/2 | 300 | 150 | 225 | 371/2 | 67/8 | - | 1 3/4 | 56 | T |
| KW200 | 3 | 300 | 200 | 225 | 383/8 | 75/8 | - | 2 1/8 | 58 | T |
| KW250 | 3 | 300 | 250 | 225 | 441/4 | 75/8 | - | 2 1/8 | 70 | T |
| KW300 | 4 FLG. | 225 | 300 | 225 | 72 | 213/4 | 57 | 15 | 450 | F |
| KW450 | 6 FLG. | 225 | 450 | 225 | 85 | 207/8 | 68 | 15 | 500 | F |
NOTES:
OPTIONS:
| System Component Selection (Typical) | *Compressors w/Aftercooler | |||||||
| Aqua
Saver Heat Exchanger |
Pumping System | Trim Cooler | Water Reg. Valve | Mixing Valve |
Max B.H.P @95°F (Max). |
Max B.H.P. @105°F (Max) |
||
| Model Number | SP/DP | KFH- | in. | mm | in. | mm. | Ambient | Ambient |
| AS48H | 33 | 100 | 3/8 | 10 | 1/2 | 12 | 20 | 15 |
| AS78H | 33 | 100 | 3/8 | 10 | 1/2 | 12 | 30 | 25 |
| AS102H | 50 | 100 | 3/8 | 10 | 1/2 | 12 | 35 | 30 |
| AS156H | 75 | 150 | 3/8 | 10 | 3/4 | 20 | 46 | 35 |
| AS205H | 75 | 200 | 1/2 | 12 | 3/4 | 20 | 58 | 46 |
| AS236H | 75 | 250 | 1/2 | 12 | 1 | 25 | 69 | 58 |
| AS343V | 100 | 300 | 3/4 | 20 | 1 | 25 | 115 | 87 |
| AS449V | 150 | 400 | 3/4 | 20 | 1 1/4 | 30 | 145 | 115 |
| AS522V | 200 | 500 | 1 | 25 | 1 1/4 | 30 | 173 | 144 |
| AS674V | 300 | 650 | 1 | 25 | 1 1/4 | 30 | 230 | 175 |
| AS783V | 300 | 800 | 1 1/4 | 30 | 1 1/2 | 40 | 250 | 200 |
| AS898V | 300 | 800 | 1 1/4 | 30 | 1 1/2 | 40 | 288 | 230 |
| AS965V | 500 | 1000 | 1 1/2 | 40 | 2 | 50 | 300 | 250 |
| AS1044V | 500 | 1000 | 1 1/2 | 40 | 2 | 50 | 345 | 288 |
| AS1100V | 500 | 1250 | 1 1/2 | 40 | 2 | 50 | 375 | 300 |
| AS1347V | 500 | 1250 | 2 | 50 | 2 | 50 | 460 | 345 |
| AS1448V | 750 | 1600 | 2 1/2 | 60 | 2 1/2 | 60 | 490 | 375 |
| AS1566V | 750 | 1600 | 2 1/2 | 60 | 2 1/2 | 60 | 518 | 400 |
| AS1796V | 750 | 2000 | 2 1/2 | 60 | 2 1/2 | 60 | 575 | 450 |
| AS1931V | 750 | 2000 | 2 1/2 | 60 | 2 1/2 | 60 | 650 | 500 |
| AS2088V | 750 | 2000 | 2 1/2 | 60 | 2 1/2 | 60 | 690 | 550 |
| AS2200V | 750 | 2500 | 2 1/2 | 60 | 3 | 75 | 800 | 650 |
| AS2500V | 750 | 3000 | 2 1/2 | 60 | 3 | 75 | 900 | 750 |
| AS2846V | 750 | 3000 | 2 1/2 | 60 | 3 | 75 | 950 | 800 |
| AS2975V | 1500 | 3000 | 2 1/2 | 60 | 3 | 75 | 1050 | 850 |
| * For compressors without After Coolers multiply B.H.P. above by: | ||||
| Type | Comp. W/A.C. | 1-Stage | 2-Stage | Rotary |
| BTUH/BHP | 2550 | 900 | 1560 | 2000 |
| Multiply BHP by | 1 | 2.83 | 1.63 | 1.27 |
AquaSaver Specifications
The packaged, single-skid, closed-loop system shall include...
Air-cooled Heat Exchanger
High-efficiency heat exchangers shall cool larger water flows with minimum pressure drop by using atmospheric air as the cooling medium. The cooling capacity to HP ration shall be maximum.
- Coil: aluminum fins, copper tubes
- Legs: galvanized steel
- Housing: aluminum
- Motors shall be direct-drive, amply sized to handle designed load conditions.
Specially designed heavy-gauge aluminum blade fans shall be statically and dynamically balanced for vibration-free operation. Fans shall be protected with coated safety guards. Number of fans shall be _______, each _______ H.P. Fans shall cycle to save energy and provide temperature control. All connections shall be factory wired to the junction box on the housing exterior or to the control panel. The heat exchanger shall be Pioneer model___________
Simplex Pumping Station
Unit shall include a pump, expansion tank, starter, NEMA 1 control panel, power-on light, on/off switch, water-out pressure gauge, and water-out temperature gauge. The pumping station shall be Pioneer model__________
Trim Cooler
The Trim Cooler shall be tube and shell design. Tubes, shell and baffles shall be of rust-free materials: copper and/or brass. The trim cooler shall be Pioneer model______________
Options:
Unit shall include two pumps, an expansion tank, two check valves (one for each pump), starters, NEMA 1 control panel, power-on light, on/off switch, water-out pressure gauge and water-out temperature gauge. Additionally, each pump shall be piped with two isolation valves, one on the suction side and one on the discharge side, so that either of the pumps can be removed from the piping system and replaced without having to shut down the system. All components shall be prepiped, wired and mounted on a skid.
The Duplex Pumping Station shall be Pioneer model _________________
|
|

Pumping Stations and Data
| Simplex | Duplex... greater reliability |
Includes -
|
Includes -
|
The following figure shows the typical pump curves.

Simplex and Duplex Pumping Stations Data
|
Model SP- DP- |
HP | Dimensions |
Expans. Tank |
Water | Approx. Shipping Wt. | |||||||
| Simplex (SP) | Duplex (DP) | |||||||||||
| Width x Depth x Height | Width x Depth x Height | IN/OUT | Simplex | Duplex | ||||||||
| IN | MM | IN | MM | Gal | Lit. | NPT IN | LBS | KGS | LBS | KGS | ||
| 33 | 1/3 | 34 x 27 x 48 | 864 x 686 x 1219 | 57 x 30 x 48 | 1448 x 762 x 1219 | 6 | 23 | 1 1/4 | 300 | 136 | 590 | 268 |
| 50 | 1/2 | 34 x 27 x 48 | 864 x 686 x 1219 | 57 x 30 x 48 | 1448 x 762 x 1219 | 6 | 23 | 1 1/4 | 350 | 159 | 690 | 313 |
| 75 | 3/4 | 34 x 27 x 48 | 864 x 686 x 1219 | 57 x 30 x 48 | 1448 x 762 x 1219 | 6 | 23 | 1 1/4 | 385 | 175 | 750 | 340 |
| 100 | 1 | 34 x 27 x 83 | 864 x 686 x 2108 | 57 x 30 x 83 | 1448 x 762 x 2108 | 10 | 38 | 1 1/2 | 495 | 225 | 895 | 406 |
| 150 | 1 1/2 | 34 x 27 x 83 | 864 x 686 x 2108 | 57 x 30 x 83 | 1448 x 762 x 2108 | 10 | 38 | 2 | 535 | 283 | 990 | 449 |
| 200 | 2 | 34 x 27 x 83 | 864 x 686 x 2108 | 57 x 30 x 83 | 1448 x 762 x 2108 | 10 | 38 | 2 | 595 | 270 | 1090 | 494 |
| 300 | 3 | 39 x 31 x 47 | 991 x 787 x 1194 | 63 x 35 x 48 | 1600 x 889 x 1219 | 15 | 57 | 2 | 695 | 315 | 1290 | 585 |
| 500 | 5 | 39 x 31 x 47 | 991 x 787 x 1194 | 63 x 35 x 48 | 1600 x 889 x 1219 | 15 | 57 | 21/2 | 795 | 360 | 1390 | 631 |
| 750 | 7 1/2 | 39 x 31 x 47 | 991 x 787 x 1194 | 63 x 35 x 48 | 1600 x 889 x 1219 | 21 | 79 | 3 | 890 | 403 | 1490 | 676 |
| 1000 | 10 | 45 x 34 x 47 | 1143 x 864 x 1194 | 78 x 44 x 48 | 1981 x 1118 x 1219 | 21 | 79 | 4 FLG. | 990 | 449 | 1790 | 812 |
| 1500 | 15 | 45 x 34 x 47 | 1143 x 864 x 1194 | 78 x 44 x 48 | 1981 x 1118 x 1219 | 21 | 79 | 4 FLG. | 1095 | 497 | 1990 | 903 |
| 2000 | 20 | 48 x 36 x 56 | 1219 x 914 x 1422 | 84 x 48 x 56 | 2134 x 1219 x 1422 | 42 | 159 | 6 FLG. | 1295 | 587 | 2290 | 1039 |
| 2500 | 25 | 48 x 36 x 56 | 1219 x 914 x 1422 | 84 x 48 x 56 | 2134 x 1219 x 1422 | 42 | 159 | 6 FLG. | 1395 | 633 | 2490 | 1129 |
| 3000 | 30 | 48 x 36 x 56 | 1219 x 914 x 1422 | 84 x 48 x 56 | 2134 x 1219 x 1422 | 42 | 159 | 6 FLG. | 1495 | 678 | 2690 | 1220 |
| 4000 | 40 | 52 x 40 x 60 | 1320 x 1016 x 1524 | 90 x 70 x 60 | 2286 x 1778 x 1524 | 80 | 303 | 6 FLG. | 1695 | 769 | 2950 | 1356 |
| 5000 | 50 | 52 x 40 x 60 | 1320 x 1016 x 1524 | 90 x 70 x 60 | 2286 x 1778 x 1524 | 80 | 303 | 8 FLG. | 1795 | 814 | 3250 | 1492 |
NOTES:
- Maximum ambient temperature: 95 Deg. F/35 Deg. C
- Minimum ambient temperature: 0 Deg. F/-18 Deg. C
- Water temperature required: 95 Deg. F/35 Deg. C or lower
- City water available @ 70 Deg. F/21 Deg. C
- Heat load (Q) = 100 x 2550 = 255,000 BTUH
A screw compressor may run into motor service factor at peak loads, therefore we shall plan a cooling system with a capacity of 1.15 x 255,000 = 293,250 BTUH.
The Aqua Saver alone will not cool water to 95 Deg.F when the ambient temperature reaches 95 Deg. F, so we shall include a Trim Cooler to provide partial cooling at peak temperatures.
Let us assume the system is adjusted to 20 GPM flow at 95 Deg. F to compressor. At peak ambient temperature, the Aqua Saver may cool water from 125 Deg. F to 102 Deg. F and the Trim Cooler further cools it to 95 Deg. F. At these conditions, the Aqua Saver will remove 20 x 500 x 23 = 230,000 BTUH and the Trim Cooler will remove 63,250 BTUH. Since the objective is to minimize cooling water usage by the Trim Cooler, we will size the Aqua Saver for 10-15 Deg. F approach temperature (0.7 correction factor-see correction factors table).
The Aqua Saver shall have a minimum capacity of 230,000 / 0.7 = 328,571 BTUH.
We recommend AS343V.
Now, we will size the Trim Cooler to handle 63,250 BTUH:
Pioneer Model KFH300 is recommended (see Trim Cooler selection table).
Conclusion: Recommended Aqua Saver Packaged system ASP343V
The system includes AS343V heat exchanger, KFH300 Trim Cooler and SP100 pumping system.
Notes:
| MODEL |
CAPACITY x 1000 |
FANS | WATER | DIMENSIONS-(INS ,MM) | FLUID CAPACITY | APPROX. SHPG./OPER. | ||||||||
| BTU/HR | K.CAL/HR | (HP) | IN/OUT | OAW | OAD | OAH | GALS | LITERS | LBS. | KGS | ||||
| AS48H | 48 | 12.1 | 1(1/2) | 1"MPT | 33 | 839 | 36 | 915 | 41 | 1,042 | 22 | 83 | 165 | 75 |
| AS78H | 78 | 19.7 | 1(1/2) | 1"MPT | 38 | 966 | 36 | 915 | 46 | 1,169 | 23 | 87 | 188 | 86 |
| AS102H | 102 | 25.7 | 1(1/2) | 1"MPT | 38 | 966 | 36 | 915 | 46 | 1,169 | 25 | 95 | 204 | 93 |
| AS156H | 156 | 39.3 | 2(1/2) | 11/4"MPT | 71 | 1,804 | 36 | 915 | 46 | 1,169 | 28 | 106 | 303 | 138 |
| AS205H | 205 | 51.7 | 2(1/2) | 11/4"MPT | 71 | 1,804 | 36 | 915 | 46 | 1,169 | 30 | 114 | 328 | 149 |
| AS236H | 236 | 59.5 | 2(1/2) | 11/4"MPT | 71 | 1,804 | 36 | 915 | 46 | 1,169 | 32 | 121 | 352 | 160 |
| AS343V | 343 | 86.4 | 2(1) | 11/2"MPT | 88 | 2,236 | 64 | 1,626 | 46 | 1,169 | 41 | 155 | 649 | 295 |
| AS449V | 449 | 113.1 | 2(1) | 2"MPT | 88 | 2,236 | 64 | 1,626 | 46 | 1,169 | 53 | 201 | 709 | 322 |
| AS522V | 522 | 131.5 | 2(1) | 2"MPT | 88 | 2,236 | 64 | 1,626 | 46 | 1,169 | 55 | 208 | 791 | 359 |
| AS674V | 674 | 169.5 | 3(1) | 21/2"MPT | 112 | 2,845 | 64 | 1,626 | 46 | 1,169 | 70 | 265 | 972 | 441 |
| AS783V | 783 | 197.3 | 3(1) | 21/2"MPT | 112 | 2,845 | 64 | 1,626 | 46 | 1,169 | 74 | 280 | 1,062 | 482 |
| AS898V | 898 | 226.3 | 4(1) | 21/2"MPT | 118 | 2,998 | 89 | 2,261 | 46 | 1,169 | 78 | 295 | 1,243 | 564 |
| AS965V | 965 | 243.2 | 4(1) | 21/2"MPT | 118 | 2,998 | 89 | 2,261 | 46 | 1,169 | 80 | 303 | 1,284 | 583 |
| AS1044V | 1,044 | 263.1 | 4(1) | 21/2"MPT | 118 | 2,998 | 89 | 2,261 | 46 | 1,169 | 85 | 322 | 1,365 | 620 |
| AS1100V | 1,100 | 277.2 | 4(1) | 21/2"MPT | 118 | 2,998 | 89 | 2,261 | 46 | 1,169 | 90 | 341 | 1,420 | 645 |
| AS1347V | 1,347 | 339.4 | 6(1) | 3"MPT | 169 | 4,293 | 89 | 2,261 | 46 | 1,169 | 100 | 379 | 1,746 | 792 |
| AS1448V | 1,448 | 364.9 | 6(1) | 3"MPT | 169 | 4,293 | 89 | 2,261 | 46 | 1,169 | 105 | 398 | 1,809 | 821 |
| AS1566V | 1,566 | 394.6 | 6(1) | 3"MPT | 169 | 4,293 | 89 | 2,261 | 46 | 1,169 | 110 | 416 | 1,929 | 875 |
| AS1796V | 1,796 | 452.6 | 8(1) | 4"FLG | 220 | 5,588 | 89 | 2,261 | 46 | 1,169 | 125 | 473 | 2,266 | 1,028 |
| AS1931V | 1,931 | 486.6 | 8(1) | 4"FLG | 220 | 5,588 | 89 | 2,261 | 46 | 1,169 | 130 | 492 | 2,349 | 1,066 |
| AS2088V | 2,088 | 526.2 | 8(1) | 4"FLG | 220 | 5,588 | 89 | 2,261 | 46 | 1,169 | 140 | 530 | 2,510 | 1,139 |
| AS2200V | 2,200 | 554.4 | 8(1) | 4"FLG | 220 | 5,588 | 89 | 2,261 | 46 | 1,169 | 145 | 549 | 2,620 | 1,189 |
| AS2500V | 2,500 | 630 | 10(1) | 4"FLG | 220 | 5,588 | 89 | 2,261 | 46 | 1,169 | 150 | 568 | 2,751 | 1,248 |
| AS2846V | 2,846 | 717.2 | 12(1) | 4"FLG | 261 | 6,630 | 89 | 2,261 | 46 | 1,169 | 155 | 587 | 3,124 | 1,418 |
| AS2975V | 2,975 | 749.7 | 12(1) | 4"FLG | 261 | 6,630 | 89 | 2,261 | 46 | 1,169 | 160 | 606 | 3,256 | 1,477 |
NOTES :
The chemically inhibited fluid is designed to provide freeze, burst and corrosion protection as well as efficient heat transfer. The fluid is fluorescent pink providing easy leak detection.
The special corrosion inhibitor in the fluid coats the metal surfaces to prevent acid formation from normal oxidation. This reduces maintenance costs and extends the life of process equipment. Freeze-Protector is available in 55-gallon and 5-gallon drums.
Installation
The Selection For Air Compressors table lists the configurations for the different models of Air Compressors.
|
|
|||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
|
||||||||||||||||||||||||||||||
÷