AquaSaver
Closed-loop Clean Water Cooling System

Closed-loop systems eliminate water loss by evaporation and algae & bacteria problems. 

Benefits AquaSaver Specifications Air-Cooled Heat Exchanger Data
AquaSaver Systems AS Packaged Systems Energy Saving Control Panel 
Optional Features Typical Installation Freeze Protector
Kleen-Water Filters and Data Pumping Stations and Data Additional Data
Selection for Air Compressors Sizing Example  Ten-Year Limited Warranty
  Trim Cooler Selection  

Benefits

Ç(back to top)


 AquaSaver Packaged Systems (ASP series)

  1. Aqua Saver heat exchanger
  2. Fan cycling
  3. Simplex or Duplex pumping station
  4. Trim Cooler with water regulating valve
  5. All prewired and prepiped on a single skid

Energy Saving Control Panel

Standard in ASP series and optional in AS series heat exchangers. Includes power-on/off switch, power-on indicator, fan motor starter(s), and fan cycling thermostat. Fan cycling saves energy and provides temperature control under varying load and ambient conditions. 


Optional Features

Ç(back to top)


Kleen-Water Filters and Data

 For longevity and dependability, we recommend Kleen-Water Filters which are 99.0% efficient down to 1 micron. For point of installation see Typical Aqua Saver installation.

MODEL PORT SIZE MAX.PRESS. MAX  MAX TEMP DIMENSIONS APPROX.
SHIPPING WT.
TYPE
INCHES
NPT-IN PSIG GPM Deg. F A B C D (LBS)
KW25 1 300 25 225 161/4 41/2 - 15/16 15 T
KW50 1 1/2 300 50 225 205/8 57/16 - 1 1/4 20 T
KW100 2 1/2 300 100 225 273/4 67/8 - 1 3/4 35 T
KW150 2 1/2 300 150 225 371/2 67/8 - 1 3/4 56 T
KW200 3 300 200 225 383/8 75/8 - 2 1/8 58 T
KW250 3 300 250 225 441/4 75/8 - 2 1/8 70 T
KW300 4 FLG. 225 300 225 72 213/4 57 15 450 F
KW450 6 FLG. 225 450 225 85 207/8 68 15 500 F

NOTES:

1. Filters come with initial element(s).
2. To order spare element, add 'E' before filter Model Number.
3. Larger sizes, built to specifications.

 OPTIONS:

  1. Flange Connections, where not standard.
  2. Pressure Differential Lights/Contacts.
  3. Multi-Filter Assemblies with By-Pass valving.

Ç(back to top)


Selection for Air Compressors

System Component Selection (Typical) *Compressors w/Aftercooler
Aqua Saver
Heat Exchanger
Pumping System Trim Cooler Water Reg. Valve Mixing Valve Max B.H.P
@95
°F (Max).
Max B.H.P.
@105°F (Max)
Model Number SP/DP KFH- in. mm in. mm. Ambient Ambient
AS48H 33 100 3/8 10 1/2 12 20 15
AS78H 33 100 3/8 10 1/2 12 30 25
AS102H 50 100 3/8 10 1/2 12 35 30
AS156H 75 150 3/8 10 3/4 20 46 35
AS205H 75 200 1/2 12 3/4 20 58 46
AS236H 75 250 1/2 12 1 25 69 58
AS343V 100 300 3/4 20 1 25 115 87
AS449V 150 400 3/4 20 1 1/4 30 145 115
AS522V 200 500 1 25 1 1/4 30 173 144
AS674V 300 650 1 25 1 1/4 30 230 175
AS783V 300 800 1 1/4 30 1 1/2 40 250 200
AS898V 300 800 1 1/4 30 1 1/2 40 288 230
AS965V 500 1000 1 1/2 40 2 50 300 250
AS1044V 500 1000 1 1/2 40 2 50 345 288
AS1100V 500 1250 1 1/2 40 2 50 375 300
AS1347V 500 1250 2 50 2 50 460 345
AS1448V 750 1600 2 1/2 60 2 1/2 60 490 375
AS1566V 750 1600 2 1/2 60 2 1/2 60 518 400
AS1796V 750 2000 2 1/2 60 2 1/2 60 575 450
AS1931V 750 2000 2 1/2 60 2 1/2 60 650 500
AS2088V 750 2000 2 1/2 60 2 1/2 60 690 550
AS2200V 750 2500 2 1/2 60 3 75 800 650
AS2500V 750 3000 2 1/2 60 3 75 900 750
AS2846V 750 3000 2 1/2 60 3 75 950 800
AS2975V 1500 3000 2 1/2 60 3 75 1050 850
* For compressors without After Coolers multiply B.H.P. above by:
Type Comp. W/A.C. 1-Stage 2-Stage Rotary
BTUH/BHP 2550 900 1560 2000
Multiply BHP by 1 2.83 1.63 1.27

 Ç(back to top)


AquaSaver Specifications

The packaged, single-skid, closed-loop system shall include...

Air-cooled Heat Exchanger

High-efficiency heat exchangers shall cool larger water flows with minimum pressure drop by using atmospheric air as the cooling medium. The cooling capacity to HP ration shall be maximum.

  1. Multi-circuit design shall have minimum pressure drop.
  2. Coil design shall allow even air distribution and therefore minimum pressure drop.
  3. For longevity materials shall be:

Specially designed heavy-gauge aluminum blade fans shall be statically and dynamically balanced for vibration-free operation. Fans shall be protected with coated safety guards. Number of fans shall be _______, each _______ H.P. Fans shall cycle to save energy and provide temperature control. All connections shall be factory wired to the junction box on the housing exterior or to the control panel. The heat exchanger shall be Pioneer model___________

Simplex Pumping Station

Unit shall include a pump, expansion tank, starter, NEMA 1 control panel, power-on light, on/off switch, water-out pressure gauge, and water-out temperature gauge. The pumping station shall be Pioneer model__________

Trim Cooler

The Trim Cooler shall be tube and shell design. Tubes, shell and baffles shall be of rust-free materials: copper and/or brass. The trim cooler shall be Pioneer model______________

Options:

Unit shall include two pumps, an expansion tank, two check valves (one for each pump), starters, NEMA 1 control panel, power-on light, on/off switch, water-out pressure gauge and water-out temperature gauge. Additionally, each pump shall be piped with two isolation valves, one on the suction side and one on the discharge side, so that either of the pumps can be removed from the piping system and replaced without having to shut down the system. All components shall be prepiped, wired and mounted on a skid.

The Duplex Pumping Station shall be Pioneer model _________________

Ç(back to top)


AquaSaver Packaged Systems

Model

Components

ASP48H AS48H, KFH100, SP033
ASP78H AS78H, KFH100, SP033
ASP102H AS102H, KFH100, SP050
ASP156H AS156H, KFH150, SP075
ASP205H AS205H, KFH200, SP075
ASP236H AS236H, KFH250, SP075
ASP343V AS343V, KFH300, SP100
ASP449V AS449V, KFH400, SP150
ASP522V AS522V, KFH500, SP200
ASP674V AS674V, KFH650, SP300
ASP783V AS783V, KFH800, SP300
ASP898V AS898V, KFH800, SP300
ASP965V AS965V, KFH1000, SP500
Model

Components

ASP1044V AS1044V, KFH1000, SP500
ASP1100V AS1100V, KFH1000, SP500
ASP1347V AS1347V, KFH1250, SP500
ASP1448V AS1448V, KFH1600, SP750
ASP1566V AS1566V, KFH1600, SP750
ASP1796V AS1796V, KFH2000, SP750
ASP1931V AS1931V, KFH2000, SP750
ASP2088V AS2088V, KFH2000, SP750
ASP2200V AS2200V, KFH2500, SP750
ASP2500V AS2500V, KFH3000, SP750
ASP2846V AS2846V, KFH3000, SP750
ASP2975V AS2975V, KFH3000, SP1500
   

Ç(back to top)


Typical AquaSaver Installation


 Pumping Stations and Data

Simplex Duplex... greater reliability
Includes -
  • Pump
  • Starter
  • NEMA 1 control panel
  • Power-on light
  • ON/OFF switch
  • Water-out pressure gauge
  • Prepiped, prewired and mounted on a heavy skid.
Includes -
  • Two pumps
  • Two check valves (one for each pump)
  • Starters, NEMA 1 control panel, power-on light, on/off switch, water-out pressure gauge and water-out temperature gauge.
  • Additionally, each pump is piped with two isolation valves.
  • Either of the pumps can be replaced without disturbing the other.
  • All components are prepiped, prewired and mounted on a heavy skid.

 The following figure shows the typical pump curves.

 Simplex and Duplex Pumping Stations Data

Model
SP-
DP-
HP Dimensions Expans.
Tank
Water Approx. Shipping Wt.
Simplex (SP) Duplex (DP)
Width x Depth x Height Width x Depth x Height IN/OUT Simplex Duplex
IN MM IN MM Gal Lit. NPT IN LBS KGS LBS KGS
33 1/3 34 x 27 x 48 864 x 686 x 1219 57 x 30 x 48 1448 x 762 x 1219 6 23 1 1/4 300 136 590 268
50 1/2 34 x 27 x 48 864 x 686 x 1219 57 x 30 x 48 1448 x 762 x 1219 6 23 1 1/4 350 159 690 313
75 3/4 34 x 27 x 48 864 x 686 x 1219 57 x 30 x 48 1448 x 762 x 1219 6 23 1 1/4 385 175 750 340
100 1 34 x 27 x 83 864 x 686 x 2108 57 x 30 x 83 1448 x 762 x 2108 10 38 1 1/2 495 225 895 406
150 1 1/2 34 x 27 x 83 864 x 686 x 2108 57 x 30 x 83 1448 x 762 x 2108 10 38 2 535 283 990 449
200 2 34 x 27 x 83 864 x 686 x 2108 57 x 30 x 83 1448 x 762 x 2108 10 38 2 595 270 1090 494
300 3 39 x 31 x 47 991 x 787 x 1194 63 x 35 x 48 1600 x 889 x 1219 15 57 2 695 315 1290 585
500 5 39 x 31 x 47 991 x 787 x 1194 63 x 35 x 48 1600 x 889 x 1219 15 57 21/2 795 360 1390 631
750 7 1/2 39 x 31 x 47 991 x 787 x 1194 63 x 35 x 48 1600 x 889 x 1219 21 79 3 890 403 1490 676
1000 10 45 x 34 x 47 1143 x 864 x 1194 78 x 44 x 48 1981 x 1118 x 1219 21 79 4 FLG. 990 449 1790 812
1500 15 45 x 34 x 47 1143 x 864 x 1194 78 x 44 x 48 1981 x 1118 x 1219 21 79 4 FLG. 1095 497 1990 903
2000 20 48 x 36 x 56 1219 x 914 x 1422 84 x 48 x 56 2134 x 1219 x 1422 42 159 6 FLG. 1295 587 2290 1039
2500 25 48 x 36 x 56 1219 x 914 x 1422 84 x 48 x 56 2134 x 1219 x 1422 42 159 6 FLG. 1395 633 2490 1129
3000 30 48 x 36 x 56 1219 x 914 x 1422 84 x 48 x 56 2134 x 1219 x 1422 42 159 6 FLG. 1495 678 2690 1220
4000 40 52 x 40 x 60 1320 x 1016 x 1524 90 x 70 x 60 2286 x 1778 x 1524 80 303 6 FLG. 1695 769 2950 1356
5000 50 52 x 40 x 60 1320 x 1016 x 1524 90 x 70 x 60 2286 x 1778 x 1524 80 303 8 FLG. 1795 814 3250 1492

 NOTES:

Ç(back to top)


Sizing Example

Size an Aqua Saver and Trim Cooler to cool a 100 HP rotary screw compressor with an aftercooler for the following conditions:

A screw compressor may run into motor service factor at peak loads, therefore we shall plan a cooling system with a capacity of 1.15 x 255,000 = 293,250 BTUH.

The Aqua Saver alone will not cool water to 95 Deg.F when the ambient temperature reaches 95 Deg. F, so we shall include a Trim Cooler to provide partial cooling at peak temperatures.

Let us assume the system is adjusted to 20 GPM flow at 95 Deg. F to compressor. At peak ambient temperature, the Aqua Saver may cool water from 125 Deg. F to 102 Deg. F and the Trim Cooler further cools it to 95 Deg. F. At these conditions, the Aqua Saver will remove 20 x 500 x 23 = 230,000 BTUH and the Trim Cooler will remove 63,250 BTUH. Since the objective is to minimize cooling water usage by the Trim Cooler, we will size the Aqua Saver for 10-15 Deg. F approach temperature (0.7 correction factor-see correction factors table).

The Aqua Saver shall have a minimum capacity of 230,000 / 0.7 = 328,571 BTUH.

We recommend AS343V.

Now, we will size the Trim Cooler to handle 63,250 BTUH:

Pioneer Model KFH300 is recommended (see Trim Cooler selection table).

Conclusion: Recommended Aqua Saver Packaged system ASP343V

The system includes AS343V heat exchanger, KFH300 Trim Cooler and SP100 pumping system.

 Notes:

 Ç(back to top)


Air-Cooled Heat Exchanger Data

MODEL

CAPACITY x 1000

FANS WATER DIMENSIONS-(INS ,MM) FLUID CAPACITY APPROX. SHPG./OPER.
BTU/HR K.CAL/HR (HP) IN/OUT OAW OAD OAH GALS LITERS LBS. KGS
AS48H 48 12.1 1(1/2) 1"MPT 33 839 36 915 41 1,042 22 83 165 75
AS78H 78 19.7 1(1/2) 1"MPT 38 966 36 915 46 1,169 23 87 188 86
AS102H 102 25.7 1(1/2) 1"MPT 38 966 36 915 46 1,169 25 95 204 93
AS156H 156 39.3 2(1/2) 11/4"MPT 71 1,804 36 915 46 1,169 28 106 303 138
AS205H 205 51.7 2(1/2) 11/4"MPT 71 1,804 36 915 46 1,169 30 114 328 149
AS236H 236 59.5 2(1/2) 11/4"MPT 71 1,804 36 915 46 1,169 32 121 352 160
AS343V 343 86.4 2(1) 11/2"MPT 88 2,236 64 1,626 46 1,169 41 155 649 295
AS449V 449 113.1 2(1) 2"MPT 88 2,236 64 1,626 46 1,169 53 201 709 322
AS522V 522 131.5 2(1) 2"MPT 88 2,236 64 1,626 46 1,169 55 208 791 359
AS674V 674 169.5 3(1) 21/2"MPT 112 2,845 64 1,626 46 1,169 70 265 972 441
AS783V 783 197.3 3(1) 21/2"MPT 112 2,845 64 1,626 46 1,169 74 280 1,062 482
AS898V 898 226.3 4(1) 21/2"MPT 118 2,998 89 2,261 46 1,169 78 295 1,243 564
AS965V 965 243.2 4(1) 21/2"MPT 118 2,998 89 2,261 46 1,169 80 303 1,284 583
AS1044V 1,044 263.1 4(1) 21/2"MPT 118 2,998 89 2,261 46 1,169 85 322 1,365 620
AS1100V 1,100 277.2 4(1) 21/2"MPT 118 2,998 89 2,261 46 1,169 90 341 1,420 645
AS1347V 1,347 339.4 6(1) 3"MPT 169 4,293 89 2,261 46 1,169 100 379 1,746 792
AS1448V 1,448 364.9 6(1) 3"MPT 169 4,293 89 2,261 46 1,169 105 398 1,809 821
AS1566V 1,566 394.6 6(1) 3"MPT 169 4,293 89 2,261 46 1,169 110 416 1,929 875
AS1796V 1,796 452.6 8(1) 4"FLG 220 5,588 89 2,261 46 1,169 125 473 2,266 1,028
AS1931V 1,931 486.6 8(1) 4"FLG 220 5,588 89 2,261 46 1,169 130 492 2,349 1,066
AS2088V 2,088 526.2 8(1) 4"FLG 220 5,588 89 2,261 46 1,169 140 530 2,510 1,139
AS2200V 2,200 554.4 8(1) 4"FLG 220 5,588 89 2,261 46 1,169 145 549 2,620 1,189
AS2500V 2,500 630 10(1) 4"FLG 220 5,588 89 2,261 46 1,169 150 568 2,751 1,248
AS2846V 2,846 717.2 12(1) 4"FLG 261 6,630 89 2,261 46 1,169 155 587 3,124 1,418
AS2975V 2,975 749.7 12(1) 4"FLG 261 6,630 89 2,261 46 1,169 160 606 3,256 1,477

NOTES :

Ç(back to top)


Freeze-Protector 

The chemically inhibited fluid is designed to provide freeze, burst and corrosion protection as well as efficient heat transfer. The fluid is fluorescent pink providing easy leak detection.

The special corrosion inhibitor in the fluid coats the metal surfaces to prevent acid formation from normal oxidation. This reduces maintenance costs and extends the life of process equipment. Freeze-Protector is available in 55-gallon and 5-gallon drums.

 Installation

1. Clean system properly.
2. Mix with good quality water. Distilled water is recommended.

The Selection For Air Compressors table lists the configurations for the different models of Air Compressors.

Ç(back to top)


Data Tables For AquaSavers

Maximum recommended flow
Pipe Size GPM
@20 -50
PSIG
0.5" 8
0.75" 14
1.0" 23
1.25" 36
1.5" 50
2.0" 78
2.5" 120
3.0" 180
4.0" 300
5.0" 450
6.0" 600
8.0" 1200
Freezing & Boiling
Points Aqueous Solutions
Freezing
Temp. F
% Freeze
Protector (Wt)
Boiling Temp. F
26 10 14
18 20 216
7 30 220
-8 40 220
-29 50 225
-55 60 230
<-60 70 242
Typical heat transfer coefficients (U)
Tube side fluid water oil 50% freeze
Water 400 100 350
Oil 50    
50% Freeze Protector   90 300
Conversion data
1 PSI = 2.036 in. of mercury = 2.31 ft. of water
0.069 bar = 0.070 KG/cm2 = 6895 Pascal
1 Cu. Ft= 7.48 U.S. gallons = 0.0283 cu. meter = 28.32 liter
29.92 quarts = 59.84 pints = 6.233 imp. gallons
1 Lb. = 0.4536 KG
1 HP = 746 watts = 2547 BTUH = 33,000 ft. lbs./min. = 10.68 k. calories/min.
°F = 32 + (1.8 x °C)
1 BTU raises 1 lb. of water 1°F.
1 BTU raises 54 cu. ft. of air 1°F (std. press. & temp.)
1 lb. of steam raises 1 gal. of water approx. 100°F.
Heat load (Q)
Fluid Formula
Water Q = 500 x GPM x deltaT x specific heat
Oil Q = 210 x GPM x deltaT x specific heat
50% Freeze
Protector
Q = 450 x GPM x deltaT x specific heat

 Ç(back to top)