TROUBLE SHOOTING GUIDE

TROUBLE SHOOTING PHL, PHI, AND PHE DRYERS

FAILURE TO SHIFT LIGHT ON:

DRYING TOWER LOW PRESSURE UNDER 70PSI

NO AIR COMING INTO DRYER

INLET VALVE NOT OPENING

AIR ON TO INLET VALVE (VALVE CLOSES WITH AIR ON) AQUAMATIC VALVES ONLY

PURGE VALVE STUCK OPEN

REPRESSUEAZION VALVE DID NOT OPEN IF UNIT IS EQUIPPED WITH ONE

PRESSURE SWITCH DID NOT CLOSE

NO POWER FROM CONTROL BOARD TO PRESSURE SWITCH

REGENERATING TOWER HIGH PRESSURE OVER 40PSI

MUFFLER STOPPED UP

PURGE VALVE NOT OPENING

NO SIGNAL FROM CONTROL PANEL FOR PURGE VALVE TO OPEN

REPRESSUEAZION VALVE DID NOT CLOSE IF UNIT IS EQUIPPED WITH ONE

AIR ON TO PURGE VALVE (VALVE CLOSES WITH AIR ON) AQUAMATIC VALVES ONLY

PRESSURE SWITCH DID NOT CLOSE

NO POWER FROM CONTROL BOARD TO PRESSURE SWITCH

INLET VALVE NOT CLOSING OR LEAKING

OUTLET CHECK VALVE OR ACTUATED VALVE LEAKING

PURGE CHECK VALVE LEAKING

DEPRESSURIZATION VALVE DID NOT OPEN (IF DRYER IS EQUIPPED WITH THEM)

AIR IS ON AND GOING THROUGH CONTROL AIR FILTER

GENERAL ITEMS TO CHECK

PURGE ADJUSTMENT VALVE SET TO 40-45 PSI

MINIMUM INLET PRESSURE 75PSI

 

Contact Us

Pioneer Air Systems, Inc.
210 Flatfork Road
Wartburg, TN 37887, USA

T: (423) 346-6693
F: (423) 346-3865 or 7522
Email: Click Here

Testimonials

"I wanted to drop you a note to give you some feedback on the results of your customer service efforts at Texas Instruments… I am pleased to report the Texas Instruments was extremely impressed with the way that Pioneer handled their problem and were very appreciative of the efforts…"

Richard J. Brown, Jr.

AirPower of New England

"I called Pioneer to find repair parts for our R100 air dryer and was met with the most pleasant and helpful staff. I was mostly impressed as our air dryer was built in July 1988!!! First repair needed. It runs 8-10 hrs per day and does a great job. Our repairman remarked that we have some of cleanest nail/staplers guns he services."

Mike Woley

Baldwin Mfg

"I would like to personally thank you for your cooperation and help. The attention you gave to resolve problems and answer questions is commendable… This type of service is very seldom found in today's businesses."

William E. Pickering, Jr.

Central Power and Light Company

"…The dryer performed flawlessly and the customer was very happy with a pressure dew point of -89ºF… This type of service certainly does create a feeling of doing business with a first-class outfit…"

Philip Scarola

Centri Dye Equipment Company

"Your program was most educational and enjoyable."

Terry Perko

Diversified Air Systems, Inc.

"I would like to take this opportunity to commend your plant personnel (Rick Lee and Glen Ford)… they should be given a heros welcome on their performance… Please extend a "bravo & at' a boy" from all of us here in Phoenix."

Ronald Egner

George S. Thomson Company

"Our existing unit is now working well up to design capacity 60 scfm flow. Once we exceed 60 scfm we experience differential pressure issue due to freezing across the evaporators. Please quote new clean up skid for 100 scfm capacity. We would keep our existing 60 scfm unit as a back-up."

Brian Reil

Kraft Foods

"I would like to express my appreciation for the training and hospitality I received during my visit to your facility… I was most impressed by the professionalism and enthusiasm of your entire staff."

Loy McDonald

Lewis Systems South, Inc.

"I received a call from my customer the day the parts were delivered and he was very pleased and wanted to express his gratitude to me and to you and your organization. Thank you for the extra care and concern to get these items to us as required. Good Job!"

Herb Miller

Motion Industries

"Thank you for your message today, and I appreciated the opportunity to meet you and your team. The information we received was very interesting and we are excited about this opportunity… I very much appreciate your efforts to make us comfortable and welcome in your home and your business."

James D. Packard

Pacwill Environmental